Selecting a Power Supply for Industrial Automation: 24V Systems

QUICK LINK

Power solutions for factory automation, PLC systems, motor drives, CNC machines, and industrial sensors.

Industrial automation equipment is often designed for continuous operation, where unstable power or unexpected power supply failure can result in equipment faults, communication interruptions, and costly downtime. 24V DC is widely used across industrial control systems, powering equipment such as HMI panels, industrial PCs, communication devices, sensors, controllers, and other automation peripherals.

For equipment powered by an external AC/DC power supply, selecting the right 24V adapter involves more than matching voltage and wattage. Engineers must also consider continuous and peak load requirements, startup current, cable voltage drop, thermal performance, protection behavior, connector reliability, operating environment, and long-term stability.

This guide explains the key considerations for selecting 24V external power supplies for industrial automation equipment, including load and power sizing, startup and peak-current requirements, voltage drop over DC output cables, thermal and reliability considerations, connector selection, and safety and EMC requirements for different target markets.

How Do You Profile the 24V Load of Industrial Automation Equipment?

Industrial automation equipment may combine controllers, HMI panels, sensors, communication devices, and actuators with very different current characteristics. Before selecting a 24V external power supply, engineers should calculate both the continuous load and any startup or transient load expected during operation.

Typical 24V Loads

Device TypeTypical CurrentDesign Consideration
PLC / Controller0.3–0.8ADepends on CPU, integrated I/O, and configuration
Digital I/O Module0.05–0.5A+Include current drawn by connected field loads where applicable
Analog I/O Module0.1–0.3ADepends on channel count and connected devices
HMI Panel (7–10″)0.5–1.2ADisplay size, backlight, processor, and interfaces affect consumption
Proximity Sensor0.01–0.03A eachMultiply by the number of simultaneously powered sensors
Solenoid Valve0.1–0.5A eachCheck pull-in, holding, and simultaneous activation requirements
Small DC Motor / Actuator0.5–3A+Startup or stall current can be substantially higher than normal running current

Values are illustrative only. Always use the equipment manufacturer’s rated and peak-current specifications for final power-system design.

Example Load Calculation

Consider a compact automation device powered from 24V DC:

  • Controller: 0.6A
  • HMI: 0.8A
  • 10 proximity sensors: 0.2A
  • Communication and I/O electronics: 0.5A
  • Four actuators / solenoids during normal operation: 1.2A

Estimated continuous load:

0.6 + 0.8 + 0.2 + 0.5 + 1.2 = 3.3A

At 24V:

24V × 3.3A = 79.2W

If a 25% design margin is used as an initial engineering allowance:

3.3A × 1.25 = 4.13A

A 24V / 5A (120W) external power supply could therefore provide suitable continuous-power headroom, provided its transient capability, thermal performance, and operating conditions also meet the application requirements.

Check the peak-current profile of the loads and compare it with the power supply’s specified overload, peak-current, and protection characteristics. If simultaneous startup exceeds the available capability, consider load sequencing, additional power headroom, or a power supply designed for the required transient load.


24V vs. 48V Architecture in Industrial Automation Equipment

While 24V DC is widely used for industrial controls, sensors, HMI panels, communication equipment, and actuators, higher-power devices may operate at 48V DC or other voltage levels. Equipment combining both low-power control electronics and higher-power loads may therefore require a 24V architecture, 48V architecture, or mixed-voltage power system.

The choice should be based on total power, load distribution, cable length, voltage-drop limits, efficiency, component compatibility, and system reliability.

Why Consider 48V?

For the same output power, increasing the distribution voltage reduces the required current.

For example, at approximately 500W:

ArchitectureCurrent at 500WRelative Current
24V DC≈20.8A100%
48V DC≈10.4A50%

Lower current can reduce conductor requirements, connector stress, voltage drop, and resistive losses.

Because cable losses are proportional to I²R, reducing current by half can theoretically reduce resistive losses by approximately 75%, assuming the same conductor resistance.

This can make 48V attractive for higher-power equipment or applications where cable losses and current capacity become significant design constraints.

24V, 48V, or Mixed Voltage?

ArchitectureBest Suited ForKey Considerations
24V SystemPLCs, HMIs, sensors, control electronics, communication equipment, smaller actuatorsBroad industrial compatibility and simpler integration
48V SystemHigher-power actuators, motors, communication equipment, and equipment designed around 48V inputLower current for equivalent power and potentially lower distribution losses
Mixed 24V / 48V SystemEquipment combining 24V controls with higher-power 48V loadsRequires separate supplies or DC-DC conversion and additional system-level design

Separate Supplies vs. DC-DC Conversion

A mixed-voltage system can generally be implemented in two ways:

Separate Power Supplies

AC Input → 24V Supply → 24V Loads
AC Input → 48V Supply → 48V Loads

This approach can simplify voltage-domain separation and avoid conversion losses between the 48V and 24V sections.

48V Distribution with DC-DC Conversion

AC Input → 48V Supply → 48V Loads
           ↓
       48V → 24V DC-DC → 24V Loads

This architecture can reduce current in the main distribution path but introduces an additional conversion stage.

The DC-DC converter must be evaluated for:

  • Output power and peak load
  • Conversion efficiency
  • Thermal performance
  • Input and output voltage range
  • Protection behavior
  • Isolation requirements
  • EMC performance
  • Operating environment
  • Long-term reliability

Engineering Note

Higher voltage reduces current for the same power, but it does not automatically make 48V the better architecture.

If most equipment operates at 24V, a direct 24V supply may provide the simplest and most efficient solution. If a significant portion of the system requires higher power at 48V, a 48V or mixed-voltage architecture may reduce distribution current and improve overall system integration.

The final architecture should be selected based on the actual load profile and system requirements, rather than fixed thresholds for power, cable length, or percentage of 48V loads.

The appropriate voltage architecture should therefore be evaluated at the system level, not from distribution voltage alone.

What Cable and Voltage Drop Considerations Apply to 24V Power Systems?

Voltage drop is an important consideration in 24V DC systems because even a relatively small loss in the cable reduces the voltage available at the equipment.

The actual voltage at the load depends on output current, conductor resistance, cable length, connector resistance, and the power supply output voltage. For industrial equipment, cable design should therefore be evaluated under maximum expected operating load rather than assumed from the nominal 24V rating.

Understanding Voltage Drop

For a two-conductor DC cable, voltage drop can be estimated as:

Vdrop = 2 × L × R × I

where:

  • L = one-way cable length
  • R = conductor resistance per unit length
  • I = load current

The factor of 2 accounts for both the outgoing and return conductors.

As current or cable length increases, voltage drop increases. A larger conductor reduces resistance and therefore reduces both voltage drop and cable power loss.

Example: 24V Cable Voltage Drop

The following examples use approximate copper conductor resistance at 20°C and assume the stated distance is the one-way cable length.

LoadCableOne-Way LengthApprox. Voltage DropApprox. Drop
24V / 5A14 AWG30m≈2.5V≈10.4%
24V / 5A12 AWG50m≈2.6V≈10.8%
24V / 10A10 AWG30m≈2.0V≈8.2%
24V / 10A12 AWG20m≈2.1V≈8.7%

Values are illustrative. Actual conductor resistance increases with temperature and can also be affected by cable construction, connectors, terminals, and manufacturing tolerances.

These examples show why long cable runs and higher currents can become problematic in a 24V system even when the power supply itself maintains accurate output regulation.

For External 24V Power Adapters

For equipment powered by an external AC/DC adapter, the most practical approach is usually to optimize the DC output cable rather than design around long-distance DC distribution.

Key variables include:

  • Cable length
  • Wire gauge
  • Maximum continuous current
  • Peak current
  • Connector resistance
  • Allowable voltage drop
  • Cable temperature rise

Higher-current or longer-cable applications may require a larger conductor, shorter cable, lower-resistance connector, or a power supply configuration designed to compensate for the expected line loss.

Engineering Example

Consider a 24V / 5A industrial power adapter.

If the equipment requires a relatively long DC output cable, using a small conductor can produce excessive voltage drop at full load. Increasing the conductor size reduces resistance and helps maintain adequate voltage at the equipment input.

For this reason, cable length and AWG should be specified together with the output current—not selected independently.

Engineering Note

The power supply output may be 24.0V, but the equipment only receives the voltage remaining after cable and connector losses.

Always calculate or measure voltage at the load under the expected operating conditions. The allowable voltage drop should be based on the equipment manufacturer’s specified input-voltage range rather than a universal 3%, 5%, or 10% rule.

For applications requiring long-distance 24V distribution, multiple cabinets, or high branch currents, system-level power distribution should be evaluated separately from the external power adapter itself.

What Protection and Reliability Features Are Critical for Industrial 24V Supplies?

Industrial automation equipment often operates continuously and may experience startup surges, short circuits, overloads, elevated temperatures, and disturbances from the AC power network. A 24V power supply should therefore provide appropriate protection while maintaining stable operation under expected load and environmental conditions.

Core Protection Functions

ProtectionPurposeEngineering Consideration
Overcurrent Protection (OCP)Limits excessive output current during overload conditionsTrip threshold and recovery behavior should accommodate normal startup and peak loads without nuisance shutdown
Overvoltage Protection (OVP)Prevents excessive output voltage from reaching connected equipmentThreshold should remain above normal regulation limits but below levels that could damage the load
Short-Circuit Protection (SCP)Protects the supply and wiring during an output short circuitThe supply should safely limit or interrupt output and recover according to the intended application
Overtemperature Protection (OTP)Prevents damage when internal temperatures exceed safe operating limitsThreshold and recovery behavior depend on component ratings, thermal design, and operating environment
Reverse / Backfeed ProtectionProtects against unintended reverse current or polarity conditions where applicableParticularly relevant to battery-backed, redundant, field-wired, or multi-source power systems

Protection behavior is as important as the threshold itself. Depending on the application, the supply may use hiccup, constant-current, foldback, auto-recovery, or latching protection.

The appropriate strategy should be selected according to the load characteristics and system-level fault response.

Reliability Considerations

For industrial applications, reliability should be evaluated through more than the nominal output rating.

Key indicators may include:

  • MTBF data, with the calculation method and operating temperature clearly specified
  • High-temperature, long-life electrolytic capacitors with appropriate derating
  • Thermal margin at continuous rated load
  • Burn-in or production stress screening, where used by the manufacturer
  • Component derating for voltage, current, power, and temperature
  • Surge and transient immunity appropriate to the intended environment
  • Protection verification under overload, short-circuit, and abnormal operating conditions

MTBF and Component Lifetime

MTBF is a statistical reliability estimate, not the expected lifetime or guaranteed service life of an individual power supply.

When comparing power supplies, OEMs should review the calculation methodology, operating temperature, load conditions, and assumptions behind the published MTBF value rather than comparing the headline number alone.

Capacitor specifications should be evaluated in the same way. A capacitor rated for thousands of hours at its maximum temperature can achieve substantially longer service life when operated at a lower actual temperature, making thermal design and component placement critical to long-term reliability.

Surge & EMC Immunity

Industrial environments may expose power supplies to electrical disturbances generated by switching equipment, motors, contactors, or the AC distribution network.

Testing such as IEC 61000-4-5 surge immunity can be relevant, but the required test level should be determined by the applicable product standard, installation environment, equipment category, and target market rather than treated as a universal industrial requirement.

Engineering Note

A protection function is only effective when its threshold and response behavior match the actual load and system requirements.

For example, an OCP threshold that is too low may cause nuisance shutdown during actuator startup, while a threshold that is too high may provide insufficient protection during a sustained overload.

Likewise, whether OVP should latch or automatically recover depends on the system architecture and risk assessment. Critical equipment may benefit from a latched shutdown requiring deliberate intervention, while automatic recovery may be appropriate where temporary disturbances are expected and unattended recovery is desirable.

Redundancy and Parallel Operation Considerations

Critical automation equipment may require redundant power architecture to maintain operation if one power supply fails. Common approaches include 1+1 redundancy, where either supply can support the full load, and N+1 redundancy, where additional power capacity allows the system to continue operating after the loss of one supply.

1+1 Redundancy

In a 1+1 architecture, two power supplies are sized so that either unit can support the required load.

Power Supply A → Isolation / OR-ing → 24V Load
Power Supply B → Isolation / OR-ing → 24V Load

Output isolation prevents a fault or reverse-current condition in one supply from adversely affecting the other source.

Depending on the design, isolation may be implemented using OR-ing diodes, MOSFET-based ideal-diode circuits, external redundancy modules, or integrated reverse-current protection.

Any voltage drop and power loss introduced by the isolation stage should be included in the system power budget.

Parallel Operation

Parallel operation is different from simply connecting two power supplies together.

When multiple supplies are intended to share the load during normal operation, they should be specifically designed or approved for parallel operation and current sharing.

Without appropriate sharing control, small differences in output voltage can cause one supply to carry substantially more current than the other, potentially leading to thermal stress, protection activation, or reduced reliability.

ArchitecturePurposeKey Requirement
1+1 RedundancyMaintain operation after one supply failsEach supply can support the required load; appropriate output isolation
N+1 RedundancyProvide fault tolerance in higher-power systemsSufficient remaining capacity after one supply fails
Parallel OperationIncrease available output current or distribute loadSupplies must explicitly support parallel/current-sharing operation

Monitoring & Fault Detection

For critical equipment, redundancy should also include a method of detecting when one power source has failed.

Useful monitoring functions may include:

  • AC input status
  • DC output status
  • Power-good signal
  • Alarm relay
  • Overtemperature indication
  • Communication or remote monitoring interface

Without fault monitoring, a redundant system may continue operating on the remaining supply while the failed unit goes unnoticed, leaving the system without redundancy until the next failure.

Engineering Note

Do not assume that two standard power supplies can be connected directly in parallel.

Power supplies used in redundant or parallel architectures should be evaluated for reverse-current behavior, output isolation, current sharing, fault response, protection interaction, and manufacturer-approved parallel operation.

For systems using external desktop adapters, redundancy is typically implemented at the system level using appropriate isolation or power-path management rather than by directly connecting adapter outputs together.

Conclusion

Selecting a 24V power supply for industrial automation equipment requires more than matching voltage and wattage. Engineers should evaluate continuous and peak load, cable voltage drop, thermal performance, protection behavior, connector reliability, operating environment, and redundancy requirements as part of the complete power system.

For many OEM applications, the most effective solution is a proven power platform with sufficient electrical and thermal margin, combined with the appropriate DC cable, connector, protection strategy, and market-specific compliance. Where higher power or mixed-voltage loads are involved, 24V and 48V architectures should be evaluated at the system level to determine the most practical solution.

24V & 48V Power Solutions for Industrial Equipment

YHYadapter provides 24V and 48V AC/DC power solutions for industrial automation equipment and peripherals, including desktop power adapters and customized OEM/ODM configurations. Available options include different power levels, DC cables, connectors, output configurations, enclosure designs, and application-specific requirements.

Safety, EMC, and market-access certifications—including UL, ETL, CE, FCC, and other regional approvals—are available depending on the model, configuration, and target market.

Need a 24V or 48V power solution for your industrial equipment?
Share your required voltage, continuous and peak current, connector, cable length, application, target market, and expected volume with our engineering team to evaluate the most suitable power platform and customization approach.